DEU ENG RUS ITA DAN ! Installation Connection plan 2-pipes in parallel operation – Control by AR 6010 KD DS 1000 Supply line 230 V AC 50 - 50 Hz 127041 AR 6010 KD The switch must be closed for the cooling application! Motor Motor Service LED 2 Heating actuation 54 Service LED 2 Heating actuation All QSK HK must be connected in parallel. Ring closing and star connection are inadmissible. The power current at the same supply line must not exceed 6 A! Depending on the circumstances on site, additional mains infeed points must be provided!

Installation Parallel operation of several QSK – building management system 0 - 10 V (BMS) BMS Mains connection 230 V/AC Max. fuse 6 A min. NYM 3 x 1.5 mm2 GLT I-Y(ST)Y 2 x 2 x 0.8 mm Control line I-Y(ST)Y recommended 2 x 2 x 0.8 mm 55 QSK HK Slaves GS 2000 QSK HK Slaves GS 2000 Incoming / outgoing line 230 V AC recommended NYM-J 3 x 1.5 mm2 Max. overall length of the control line 100 m QSK HK Master GS 2000 Max. 100 m of control line QSK HK Slaves GS 2000 Max. 15 GS 2000 in one group for activation! windowside windowside windowside For a parallel operation of several QSK HK, all further QSK HK can be completely wired. All devices are synchronised via the internal communication bus. And controlled by the BMS. The BMS may only be connected to one convector. The max. control line length must not exceed 100 m, starting from the master. QSK HK Slaves GS 2000 124645.1223 QSK HK 260 | 320 | 360 DEU ENG RUS ITA DAN

Installation<br />

Parallel operation of several <strong>QSK</strong> – building management system 0 - 10 V (BMS) BMS<br />

Mains connection<br />

230 V/AC Max. fuse<br />

6 A<br />

min. NYM 3 x<br />

1.5 mm2<br />

GLT<br />

I-Y(ST)Y 2 x 2 x 0.8 mm<br />

Control line I-Y(ST)Y recommended<br />

2 x 2 x 0.8 mm<br />

55<br />

<strong>QSK</strong> <strong>HK</strong><br />

Slaves<br />

GS 2000<br />

<strong>QSK</strong> <strong>HK</strong><br />

Slaves<br />

GS 2000<br />

Incoming / outgoing line 230 V AC recommended<br />

NYM-J 3 x 1.5 mm2<br />

Max. overall length of the control line 100 m<br />

<strong>QSK</strong> <strong>HK</strong><br />

Master<br />

GS 2000<br />

Max. 100 m of control line<br />

<strong>QSK</strong> <strong>HK</strong><br />

Slaves<br />

GS 2000<br />

Max. 15 GS 2000 in one group for activation!<br />

windowside windowside windowside<br />

For a parallel operation of several <strong>QSK</strong> <strong>HK</strong>, all further <strong>QSK</strong> <strong>HK</strong> can be completely wired. All devices are synchronised via the internal communication bus. And controlled by the<br />

BMS. The BMS may only be connected to one convector. The max. control line length must not exceed 100 m, starting from the master.<br />

<strong>QSK</strong> <strong>HK</strong><br />

Slaves<br />

GS 2000<br />

124645.1223 <strong>QSK</strong> <strong>HK</strong> 260 | 320 | 360<br />