Installation<br />

Mains connection (L, N, PE)<br />

Feed in the operating voltage 230 V AC 50/60 Hz at the terminals identified<br />

with the designations L, N, . The terminals are designed for the<br />

connection of incoming/outgoing lines. This allows the supply of several<br />

devices with a single line. The maximum wire section of the mains line to<br />

the direct connection is 2.5 mm². Install multi-pole circuit breakers/safety<br />

devices with a maximum nominal current of 6 A or equivalent in the supply<br />

line, on the customer side.<br />

These safety devices must have a contact gap according to the conditions<br />

for complete separation!<br />

Connection of actuators (5 – 8)<br />

The GS 2000 is equipped with 2 outputs for the connection of thermoelectrical<br />

actuators in 24 V DC design. One each for the operating modes<br />

of heating and cooling. Connect the actuators according to the above<br />

connection plan.<br />

Connection of controls/room thermostats<br />

As a standard, the GS 2000 is controlled with the Alpha-Thermostat with<br />

integrated speed regulator (AR 6010KD-S) via the internal communication<br />

bus.<br />

Control by building management system<br />

Central DDC installations (0-10 V) can be connected to the 3 control inputs<br />

in the scope of the building management system. There are 3 separates<br />

inputs with an interior distance of 100 kOhm: Cooling, heating, speed.<br />

Functionalities as e. g. speed limitations or similar must be programmed in<br />

the BMS installation.<br />

50<br />

Electric connection as single device<br />

15 15 - 24 V DC<br />

16 16 + 24 V DC<br />

Connection strip overview<br />

1 Cooling input<br />

2 Heating input<br />

3 Speed input<br />

4 Dew point sensor<br />

7 5 Cooling actuation<br />

8 6 Heating actuation<br />

9 9 - Bus<br />

10 10 Bus A<br />

11 11 Bus B<br />

12 12 + Bus<br />

Input control<br />

230 V<br />

13<br />

L L<br />

N N<br />

14 N<br />

Mains voltage