Connection variants<br />

4.<br />

1.<br />

1.<br />

Water connection<br />

1. Variant: front side<br />

2.<br />

3.<br />

Variant: room-side<br />

Alternatively possible: through bottom plate<br />

Condensate drain<br />

4.<br />

4a.<br />

3.<br />

3.<br />

2. 2.<br />

front side connection<br />

4a. Alternatively possible: room-side<br />

47<br />

Condensate pump (option)*<br />

It is very important to clean the condensate collecting trough prior to<br />

installing the pump!<br />

Do not wire the condensate trough to the GS 2000!<br />

The Sauermann SI 1082 pump is equipped with a thermal overheating<br />

protection: Triggering at 90 °C.<br />

Pump outlet side:<br />

The pump outlet side must be connected to the waste water line with a<br />

hose with an interior diameter of 6 mm. The Sauermann accessory part<br />

ACC00205 (not included in the scope of delivery) allows a quick and easy<br />

connection of the pump pressure line to the waste water line.<br />

Water level<br />

A Alarm, 21 mm +/-2<br />

B Switch-on, 18 mm +/-2<br />

C Switching off the pump, 12<br />

mm +/-2<br />

*Please also observe the supplied instructions of the company Sauermann for the<br />

consensate pump SI 1082.<br />

C<br />

B<br />

A<br />

124645.1223 <strong>QSK</strong> <strong>HK</strong> 260 | 320 | 360<br />